HEAT DETECTOR TESTER

※CAUSION
※RISK OF ELECTRIC SHOCK UNDER STORMY WEATHER AND EXPOSED WIRES ENVIRONMENT※

※RISK OF FIRE UNDER GALE ENVIRONMENT※


Functions:

Our Heat Tester is suitable with most detectors, air is heated by the heater within the cup rapidly.

Transparent upper cup for easy observing detector LED while testing.

PC material has taken and passed the Temperature Environmental test, and can avoid deformation by working under high temperature environment continuously.


Features:

-      Suitable for most detectors

-      Design for use at height and at angles

-     Transparent upper cup enable observing detector LED Light while testing

 

Special Feature:

-    Plastic components using PC (Polycarbonate) shatterproof, high temperature and deformation resistant, suitable for usage in inspection activities.

-      Special quick locked design avoids heater movement and easy set up heat source.

-      Heater activate/ shut down rapidly

-      Heated up air indirectly, will not damage the detector.

-      Heat convection design on upper cup increase temperature quickly

-      Capable with Nohmi/Panasonic heater 


Standard Equipment

1. Heat Detector Tester * 1

2. Heater * 1

3. Heater Cover * 1

4. Instruction manual *1 

5. All-Purpose Adapter for Extension Poles *1


Specification

Heat Detector Tester - Model CC05V3

Material: Stainless Steel, Polycarbonate

Transparent PC Cup:
Inner Dia.89±1mm
Outer Dia.94±1 mm
Thickness 2.6±1mm

Height: 94mm±1

Weight: approx. 333g±1

Oil Cup Volume: 50cc ±1 (2.5hours usage)

Fuel: Cleaning Naphtha

Maximum Temp.: approx. 240℃

All-Purpose Adapter for Extension Poles: 49g


ADDITIONAL INFORMATION

  1. This product is highly electrical conductive
  2. Excessive fuel (cleaning naphtha) might lead to fire during usage, kindly remove excess fuel by upside down the fuel cup.
  3. Make sure the fuel cup is plugged-in properly. Improper placement might lead to fuel cup fall off.
  4. Do not place or store fuel and lighter under high temperature environments and  in vehicles.
  5. Do not pour liquid , rub and touch the heaters’ fabric surface.
    Improper usage of Heater might lead to invalidation. 
  6. Avoid using the Detector Testing Tool in wires exposed environment and under stormy weather.
  7. Avoid using the Detector Testing Tool under windy or gale environments.
  8. Please equip with workplace safety equipment or personal protective equipment (e.g. Safety Helmet)when using this product.
  9. Improper used ,human factors (e.g. improper storage, trample) and force majeure factors is not covered in warranty.

APPLICATION

Before Inspection:

  1. Add 50cc fuel to the oil cup, remove excess fuel.
  2. Plug-in the fuel cup, make sure it has been plugged in properly.
  3. Make sure the heater is inserted.
  4. Push the moveable cover plate to "OPEN"
  5. Ignite the heater.
  6. There will be no flame occurred, and the heaters' fabric should be combusted when ignited successfully.
  7. Air will be heated up rapidly within the cup.
  8. Plug-in the Detector Tester to the extension pole.
  9. Start Inspection.

After Inspection:

  1. Put the heater cover on the Heater for at least 1 minute.

  2. Heaters’ fabric should be in non-combustion status.
    If the heaters' fabric is still combusting, kindly unplug the oil cup.

 

TROUBLESHOOTING

Heated up Temperature too low.

  1. Movable cover plate has not push to the "OPEN" line properly.

  2. Not enough fuel.

  3. Oil cup cannot fixed to the tenon.
    This situation usually occurs when the oil cup is used to refill fuel frequently, please press the oil cup and shape it to fixed to the tenon.

  4. Oil cup cotton volume is too small to reach the bottom of the heater;
    Oil cup cotton is carbonized due to frequent usage.
    Kindly tear the carbonized part or change/fill up the cotton.

  5. The Heater absorbs the smoke testers' smoke.

    Please burn the heater by its bottom until no more smoke occurs.
    If it is still not working, it should be at the end of the lifespan, please replace it with a new heater.

Before you pay !

How we complete an order:

  1. You place the order on our website.
  2. We inquire about the freight and add it to the order.
  3. We'll inform you of the price adjustment.
  4. You can check the price and pay the order on email & our website.
  5. We will arrange the delivery very soon!


Notice:

  1. You will have to pay VAT & Tariff while goods are imported into your country.
  2. When the shipment charge shows up NTD0, please place the order first. We’ll contact you in two working days by email after inquiring about the freight and delivery days. Thank you!

This year all the world is having a different situation about the service of Cross-border logistics. To make sure we are having a fair deal including freight, we will inquire about the freight with the logistics company and confirm with you before you pay.


First time doing export.

We are a Taiwanese company founded in 1996.

Doing fire inspection for 11 years.

Devoted to the invention of fire inspection tools from 2013.

And now we are exporting our products for the first time.

We are still learning how to provide better service for our customers abroad.

If you have any advice,  please feel free to tell us anytime !




Your Cart

Your cart is currently empty.

Continue browsing here.